A/DLP-010-W-U-N-D-A-0

Differential Pressure Sensor
Automation Components (ACI) | Part Number: ADLP010WUNDA0
$133.89
Differential low pressure sensor with a 0-1", 2", 5", 10" range. Includes din rail clip, LCD display and pilot tube.
Ships in 4-6 weeks
The hinged cover on the DLP can be easily opened using the integrated locking tab on the side of the enclosure. This allows for easy access to the zero function and field selectable ranges and outputs.

A/DLP-010-W-U-N-A-3 Technical Data

Supply Voltage VDC
4-20 mA Output: 16-36 VDC (250 Ohm Load max.) / 22-36 VDC (500 Ohm Load maximum)
0-5 VDC / 0-10 VDC Output: 16-36 VDC / 24 VAC (+/- 10%)

Supply Current
4-20 mA Output: 24 mA minimum
0-5 VDC / 0-10 VDC Output: 6 mA maximum

Output Signals
Current Output: 4-20 mA, 2-Wire Loop Powered (Default); Current limited to 21.5 mA maximum
Voltage Signals: 0-5 VDC / 0-10 VDC Field Selectable, 3-Wire; Output limited @ 5.25 & 10.5 VDC

Response Time
8 seconds

Output Update Rate
1 second

Pressure Ranges
See Product Ordering Grid (next page); Field Selectable Uni and Bi-Directional Ranges

Accuracy
+/- 0.50% FSO

Zero Function
Pushbutton Zero Function

Thermal Effects
+/- 0.067% FSO / F (0.12% FSO / C)

Proof Pressure and Burst Pressure
Proof: 350 inWC (87.12 kPa)
Burst: 550 inWC (136.9 kPa) for 10 inWC (2490.8 Pa)

Operating Temperature Range
-4 to 185F (-20 to 85C)

Compensated Temperature Range
32 to 122F (0 to 50C)

Storage Temperature Range
-22 to 185F (-30 to 85C)

Operating Humidity Range
10 to 95% RH, non-condensing

Media Types
Dry air or inert non-conductive gases

Enclosure Material and Flammability Rating
Flame Retardant Polycarbonate; UL94-5VA

Wiring Connections
Finger Pushbutton (Spring) Terminal Blocks; accepts 16-24 AWG wires

Conduit Knockouts
Watertight Cordgrip Installed (1/2" NPT Conduit fittings accepted when Cordgrip removed)

Pressure Fitting Material
Nickel Plated Brass or Stainless Steel

Tubing Size Accepted
1/4" O.D. x 0.170" I.D. Poly Tubing