CWLSXX

Wall Sensor
Veris Industries | Part Number: CWLSXX
$275.32
Wall mount LCD carbon dioxide sensor with a range of 0 to 2000/5000 ppm. Analog output of 4 to 20 mA or 0 to 5 (or 10) Vdc.
Ships in 4-6 weeks
Non-dispersive infrared technology (NDIR) repeatable to +/- 20 ppm +/- 1% of measured value. Integrated transducer and probe eliminates the need to install a separate pick-up tube.

CWLSXX Technical Data

Input Power
Class 2; 20 to 30 Vdc/24 Vac 50/60 Hz
100 mA max

Analog Output
4 to 20 mA (clipped and capped)
0 to 5 Vdc/ 0 to 10 Vdc (selectable)

Operating Temp Range
0 to 50 C (32 to 122 F)

Operating Humidity Range
0 to 95% RH non-condensing

Housing Material
High impact ABS plastic

Terminal Block Torque
0.2 N-m (2.0 in-lbf ) max

Terminal Block Wire Size
30 to 18 AWG (0.08 to 0.5mm^2)

CO2 TRANSMITTER
Sensor Type: Non-dispersive infrared (NDIR), diffusion sampling
Output Range: 0 to 2000/5000 ppm (programmable)
Accuracy: +/- 30 ppm +/- 2% of measured value
Repeatability: +/- 20 ppm +/- 1% of measured value
Response Time: 60 seconds for 90% step change

1 Form C SPDT
1 A@30 Vdc, resistive; 30 W max