ACI ESENSE-R
Automation Components (ACI) | Part Number: ESENSER
ESENSE-R Technical Data
Supply Voltage
24 VAC/VDC +/- 20%; 50/60Hz (Half-wave rectified)
Power Consumption
more than 1W
Electrical Connections
0.00232 in (1.5 mm) screw terminals
Operating Temperature
32F to 122F (0C to 50C)
Operating RH
0 – 95% RH Non-condensing
Warm-Up Time
1 minutes (@ full specs 15 minutes)
Accuracy
+/- 30 ppm +/- 3% of reading
Repeatability
+/- 20 ppm +/- 1% of measured value
Annual Zero Drift
+/- 0.3% of measurement range
Operating Pressure
+1.6% per 0.145 psi (1 kPa) deviation from normal pressure
Sensing Method
Single beam Non-dispersive Infrared (NDIR)
Sensor Life
More than 15
Response Time
more than 10 seconds @ 30 cc/min flow rate, more than 3 minutes diffusion time
Operating Environment
Residential, Commercial spaces
Sensing Range
0 to 2000 ppm
Extended CO2 Ranges
Up to 10,000 ppm (factory set or SADK Kit required)
Extended Range Accuracy
+/- 30 ppm and +/- 5% of reading
Coverage Area
7500 sq. ft. maximum
Mounting Height
4-6’ o the floor
Calibration
Sense air ABC algorithm (Automatic Baseline Correction)
Outputs
Standard: Out 1: 0-10V for 0 to 2000 ppm
Storage
ESENSE-R: -40 to 158F (-40 to 70C)
Enclosure
ABS, Flammability Rating UL94V-0
Room Dimensions
(H) 5.12" (130 mm) x (W) 3.35" (85.1 mm) x (D) 1.18" (30 mm)