Images are representational. Actual product may vary slightly from this image.
EV150S-396+AKRX24-EV
Belimo | Part Number: EV150S396AKRX24EV
EV0150S-396 Technical Data
Service
chilled or hot water, up to 60% glycol max (open loop/steam not allowed)
Flow Characteristic
equal percentage or linear
GPM Range
11.9-39.6
Valve Size
1.5 “ [40]
End Fitting
NPT female ends
Body
forged brass, nickel plated
Sensor Housing
forged brass, nickel plated
Ball
stainless steel
Stem
stainless steel
Stem Packing
EPDM (lubricated)
Seat
Teflon PTFE
Seat O-ring
EPDM
Characterized Disc
TEFZEL
Body Pressure Rating
360 psi
Media Temperature Range (Water)
14°F to 250°F [-10°C to 120°C]
Differential Pressure Range
5 to 50 psid or 1 to 50 psid see flow reductions chart in tech doc
Close-Off Pressure
200 psi
Inlet Length to Meet Specified Measurement Accuracy
5X nominal pipe size (NPS)
Ambient Humidity
Less then 95% RH non-condensing
Flow Measurement Tolerance
±2%
Flow Control Tolerance
±5%
Flow Measurement Repeatability
±0.5%/p>
Sensor Technology
ultrasonic with glycol and temperature compensation
Temperature Sensors
PT1000 insertion sensors w/NPT body
Temperature Measurement Tolerance
According to PT1000 DIN EN60751 ClassB
Resolution of Temperature Sensor
0.18°F (0.1°C)
Rated Impulse Voltage
actuator/sensor: 0.8 kV (in accordance with EN60730-1) kV
Rangeability
100:1
Housing
NEMA 1, UL Enclosure Type 1
Weight
9.9 lb
Remote Temperature Sensor Length
Standard: 2 ft. 7.5 in. [0.8m], 9.8 ft. [3m]
Leakage
0%
Glycol Measurement Accuracy
±5%