FXSC8CL025-0-5YRMaint

FX80 + 25 dev lic + 5 yr maint
| Part Number: FXSC8CL02505YRMaint
FX80 BASE CONTROLLER & SD CARD with LICENSE FOR 25 FIELD DEVICES / 1250 POINTS and INITIAL PURCHASE 5 YEAR SOFTWARE MAINTENANCE FOR FX80 25 - 99 FIELD DEVICES.
Ships in 4-6 weeks
The FX80 controller supports a full set of building automation features, such as scheduling, alarming, historical data collection and well as a variety of other features which are specifically designed for commercial facilities. Modern HTML5 user interface allows access via a web browser and remote access is achieved using wired or wireless connection. Uses open communication protocols, such as BACnet®, LonWorks®, and N2 protocols to manage network fields.

FX80 Supervisory Controller Technical Data

Enclosure/ Mounting
Plastic/DIN Rail

Dimension
8.5 x 6 x 2.625 in. (216 x 152 x 68 mm)

Power Supply
24 VAC/DC

Processor
TI AM3352: 1000MHz ARM® Cortex™ A8

RAM Memory
1 GB DDR3 SD RAM

Flash Memory
Removable micro-SD card with 4GB flash total storage, 2 GB user storage

Environment
Operating Temperature: -4 to 140ºF (-20 to 60ºC)
Storage Temperature: -40 to 185ºF (-40 to 85ºC)
Relative Humidity: 5 to 95%, noncondensing

Onboard
2 Ethernet 10/100 Mbps; 2 RS-485 (Isolated); 1 USB, 1 Micro USB, Fast USB Bus; Wi-Fi
Plug-in options: Dual port RS-485 (Isolated); LON FT/TP-10; RS-232

Embedded
N2, BACnet, Niagara

Onboard
None

Optional
Up to 256 by using 16 Remote I/O Modules (FXRIO16)

Local (NDIO)
None

Remote I/O
Up to 256 I/O by using 16 Remote I/O Modules (FXRIO16)

United States Compliance
UL Listed, File E207782, CCN PAZX, under UL 916, Energy Management Equipment
FCC compliant to CFR 47, part 15, subpart C, Class B

Canada Compliance
UL Listed, File E207782, CCN PAZX7, under CSA C22.2 No. 205, Signal Equipment
Industry Canada compliant to ICES-003

Europe Compliance
CE Mark – Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive.

Product Codes
LP-FXRIO16-0: 8 universal inputs, 4 relay outputs, 4 analog outputs

Dimensions
4 x 3.625 x 2.625 in. (10.16 x 9.2 x 6.7 cm)

Universal Input Types Supported
10k ohm Type 3 thermistors. Thermistor Sensor Range: -10 to 240º F (-23.3 to 115.5º C). Input accuracy is in the range of ±1% of span. Characteristic curve is customizable
0–10 V; accuracy is ±2% of span, without user calibration; uses an external resistor for current input (four provided, mounted by installer on terminal connections)
4–20 mA current loop; accuracy is ±2% of span, without user calibration; selfpowered or board-powered sensors accepted
Dry contact: V open circuit, 300- ?A short-circuit current
Pulsing dry contact at a rate of up to 20 Hz; 50% duty cycle

Digital Outputs
Form A relay contacts suitable for on/off control only; floating control not supported
Maximum voltage 30 volts AC or DC, 1/2 A maximum current rating

Analog Outputs
0–10 V DC
Minimum load supported per output is 2,500 ohms minimum or 4 mA drain maximum

Processor
Intel® Pentium® 4, 1 GHz or higher
4 x 3.625 x 2.625 in. (10.16 x 9.2 x 6.7 cm)

Operating System
32-bit: Windows® 10 Pro or Enterprise, Windows 8 Pro or Enterprise, Windows 7 Professional, Enterprise, or Ultimate, or Windows XP® Professional
64-bit: Windows® 10 Pro or Enterprise, Windows 8.1 Pro or Enterprise, Windows 8 Pro or Enterprise, Windows 7 Professional, Enterprise, or Ultimate, Windows Server 2012 Standard or Enterprise with SP2, or Windows Server® 2012 R2 Standard or Enterprise with SP2

Memory
1 GB minimum, 4 GB or more recommended for larger systems

Hard Disk
4 GB minimum, more recommended depending on archiving requirements

Network Support
Ethernet 10/100 Mbps with RJ-45 connector