JC LP-FX3021E-1

Controller
Johnson Controls | Part Number: LPFX3021E1
FX30E with BACnet MS/TP Protocol: Includes 256 MB RAM/128 MB flash, 2 10/100 Mbps Ethernet ports, 1 non-isolated RS-485 port, 1 RS-232 port, 1 NDIO port, 2 communication card option slots, embedded FX Workbench, Web User Interface, Data Recovery Services with SRAM, Niagara driver, oBIX driver, N2 driver, and BACnet MS/TP driver.
Ships in 1 business day
Features a web based interface and N2, LonWorks and BACnet communication protocols. Can be set up manage security and presentation preferences through user profiles, login IDs, and passwords.

LP-FX3021E-1 Technical Data

Enclosure/ Mounting
Plastic/DIN Rail

Dimension
6.313 x 4.820 x 2.438 in. (158.75 x 101.6 x 60.325 mm)

Power Supply
DIN Rail Power modules

Battery Backup
Data Recovery Services with SRAM (Static Random Access Memory) (optional Battery available for extended run time)

Processor
Power PC 405EX at 400 MHz

RAM Memory
256 MB RAM

JAVA Heap Memory
24 MB Heap (upgradeable to 96 MB)

Flash Memory
128 MB Flash

Environment
Operating Temperature: 0 to 50 C (32 to 122 F)
Storage Temperature: 0 to 60 C (32 to 140 F) Relative Humidity: 5 to 95%, noncondensing

Communication Ports Onboard
2 Ethernet 10/100 Mbps
1 RS-485 non-isolated
1 RS-232
2 option slots

Optional
Dual port RS-485
LON FT/TP-10
RS-232
Wireless TEC (maximum of one and disables onboard RS-232) (Release 6.x and earlier)
GPRS modem (maximum of one)
Battery-less Option Card

Embedded Network Drivers
N2, Niagara, oBIX

Optional Network Drivers
See FX Supervisory Controller Software Accessories Ordering Information (Release 6.x and Earlier) for a complete list of optional network drivers

Onboard Direct I/O
None

Optional Direct I/O
Up to 66 (by using NDIO modules)

Local (NDIO) Direct I/O
Up to 66 total I/O (through optional NDIO modules)

Remote I/O
Up to 64 I/O by using 4 Remote I/O Modules (FXRIO16)