JC NS-AHB7003-0

Network Sensor
Johnson Controls | Part Number: NSAHB70030
$446.91
Network sensor that has built-in humidity and temperature sensors. Controls temperature in 0.5 degree increments. Includes LCD screen. See product chart for more information.
Ships in 4-6 weeks
Designed to be used directly with Johnson Controls Metasys system field equipment. Comes with LCD screen that allows occupants to view the zone temperature, and view and adjust the zone temperature setpoint. Comes with modular jack.

NS-AHB7003-0 Technical Data

Supply Voltage
9.8 to 16.5 VDC; 15 VDC nominal (from SA bus)

Current Consumption
25 mA maximum (non-transmitting)

Terminations
screw terminal block

Sensor Addressing
DIP switch set from 200 to 203; factory set at 203

Wire Size
Screw terminal block models: 18 to 22 AWG (1.0 to 0.6 mm diameter); 22 AWG (0.6 mm diameter) recommended

Communication Rate
Auto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps

Mounting
Surface-mounted: 80 x 80 mm

Temperature Measurement Range
32.0F/0.0C to 104.0F/40.0C

Humidity Measurement Range
Full range: 0 to 100% RH
Calibrated range: 10 to 90% RH

Temperature Sensor Type
Local 1k ohm Platinum Resistance Temperature Detector (RTD); Class A per IEC 60751

Humidity Sensor Type
Thin film capacitive sensor

Temperature Resolution (Models with LCD)
+/- 0.5F/ +/- 0.5C

Temperature Accuracy
NS Series Network Zone Sensor: +/- 1.0F/ +/-0.6C
Temperature element only: 0.35F at 70F (0.2C at 21C)

Humidity Element Accuracy
NS-AHx700x-x, NS-BHx700x-0, and NS-MHx700x-x models: +/- 3% RH for 20 to 80% RH; +/- 6% RH for 10 to 20% and 80 to 90% RH

Time Constant
10 minutes nominal at 10 fpm airflow

Default Temperature Setpoint Adjustment Range
With LCD display: 50.0F/10.0C to 86.0F/30.0C in 0.5 increments

PIR Occupancy Sensor Motion Detection (Models with PIR Occupancy Sensor)
Minimum 94 angular degrees up to a distance of 15 ft (4.6 m); based on a clear line of sight

Ambient Conditions
Operating: 32 to 104F (0 to 40C); 10 to 90% RH, noncondensing; 85F (29C) maximum dew point
Storage with LCD display: -4 to 140F (-20 to 60C); 5 to 95% RH, noncondensing