JC NS-BTP7001-0

Network Sensor
Johnson Controls | Part Number: NSBTP70010
$118.48
Network sensor with built in temperature sensor. Controls temperature in 5 degree increments. See product chart for more information.
Ships in 4-6 weeks
Designed to be used directly with Johnson Controls Metasys system field equipment. Comes with modular jack and warmer/cooler dial.

NS-BTP7001-0 Technical Data

Supply Voltage
9.8 to 16.5 VDC; 15 VDC nominal (from SA bus)

Current Consumption
Temperature only models without LCD display: 13 mA maximum (non-transmitting)

Terminations
screw terminal block

Sensor Addressing
DIP switch set from 200 to 203; factory set at 203

Wire Size
Screw terminal block models: 18 to 22 AWG (1.0 to 0.6 mm diameter); 22 AWG (0.6 mm diameter) recommended

Communication Rate
Auto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps

Mounting
Surface-mounted or vertical wallbox-mounted: 120 x 80 mm

Temperature Measurement Range
32.0F/0.0C to 104.0F/40.0C

Temperature Sensor Type
Local 1k ohm Platinum Resistance Temperature Detector (RTD); Class A per IEC 60751

Temperature Accuracy
NS Series Network Zone Sensor: +/- 1.0F/ +/-0.6C
Temperature element only: 0.35F at 70F (0.2C at 21C)

Time Constant
10 minutes nominal at 10 fpm airflow

Default Temperature Setpoint Adjustment Range
Without LCD display: +/- 5.0F/±3.0C

Ambient Conditions
Operating: 32 to 104F (0 to 40C); 10 to 90% RH, noncondensing; 85F (29C) maximum dew point
Storage without LCD display: -40 to 158F (-40 to 70C); 5 to 95% RH, noncondensing