TEC3620-00-000

Thermostat Controller
Johnson Controls | Part Number: TEC362000000
Thermostat controller with field-selectable BACnet MS/TP or N2 networked communication and 0 to 10 VDC proportional fan coil and zoning control output.
Ships in 4-6 weeks
Two configurable binary inputs and usb port configuration. Backlit LCD touchscreen. Mobile gateway that allows user to control conditions via a mobile device.

TEC3620-00-000 Technical Data

Power requirements
19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or safety extra-low voltage (SELV)

Analog Output Rating
0 to 10 VDC into 2k ohm resistance (minimum)

Relay Contact Rating
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush, Class 2 or SELV

Auxiliary Output Rating/Triac Output
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush

Binary Inputs
Dry contact across terminal COM to terminals BI1, BI2, or COS

Analog Inputs
Nickel, platinum, A99B, 2.25k ohm negative temperature coefficient (NTC), 10k ohm NTC, 10k ohm NTC Type 3 across terminal COM to terminals R SEN or COS

Temperature Sensor Type
Local 1k ohm platinum sensor

Wire Size
18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended

MS/TP Network Guidelines
Up to 100 devices maximum per Network Automation Engine (NAE);
4,000 ft (1,219 m) maximum cable length

Temperature Range
Backlit Display: -40.0 F/-40.0 C to 122.0 F/50.0 C in 0.5 Increments
Heating Control 40.0 F/4.5 C to 90.0 F/32.0 C
Cooling Control 54.0 F/12.0 C to 100.0 F/38.0 C

Temperature Accuracy
±0.9 F/±0.5 C at 70.0 F/21.0 C Typical Calibrated

Temperature Accuracy
±0.9 F/±0.5 C at 70.0 F/21.0 C typical calibrated

Minimum Deadband
2 F/1 C between heating and cooling

Ambient Conditions
Operating:32 to 122°F (0 to 50°C); 95% RH maximum, noncondensing
Storage: -22 to 122°F (-30 to 50°C); 95% RH maximum, noncondensing