TEC3620-00-000
Johnson Controls | Part Number: TEC362000000
TEC3620-00-000 Technical Data
Power requirements
19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or safety extra-low voltage (SELV)
Analog Output Rating
0 to 10 VDC into 2k ohm resistance (minimum)
Relay Contact Rating
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush, Class 2 or SELV
Auxiliary Output Rating/Triac Output
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
Binary Inputs
Dry contact across terminal COM to terminals BI1, BI2, or COS
Analog Inputs
Nickel, platinum, A99B, 2.25k ohm negative temperature coefficient (NTC), 10k ohm NTC, 10k ohm NTC Type 3 across terminal COM to terminals R SEN or COS
Temperature Sensor Type
Local 1k ohm platinum sensor
Wire Size
18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended
MS/TP Network Guidelines
Up to 100 devices maximum per Network Automation Engine (NAE);
4,000 ft (1,219 m) maximum cable length
Temperature Range
Backlit Display: -40.0 F/-40.0 C to 122.0 F/50.0 C in 0.5 Increments
Heating Control 40.0 F/4.5 C to 90.0 F/32.0 C
Cooling Control 54.0 F/12.0 C to 100.0 F/38.0 C
Temperature Accuracy
±0.9 F/±0.5 C at 70.0 F/21.0 C Typical Calibrated
Temperature Accuracy
±0.9 F/±0.5 C at 70.0 F/21.0 C typical calibrated
Minimum Deadband
2 F/1 C between heating and cooling
Ambient Conditions
Operating:32 to 122°F (0 to 50°C); 95% RH maximum, noncondensing
Storage: -22 to 122°F (-30 to 50°C); 95% RH maximum, noncondensing