Images are representational. Actual product may vary slightly from this image.
TSENSE
Automation Components (ACI) | Part Number: TSENSE
TENSE Technical Data
Supply Voltage
12 VDC, 24 VAC/VDC, ±20% (50-60 Hz)
Power Consumption
0.35W average non-display
0.6W display version
2W maximum
Electrical Connections
0.00232^2 in screw terminals
Operating Environment
Residential and Commercial spaces
Operating Temperature
32 F to 122 F (0 C to 50 C)
Operating RH
0 – 95% RH Non-condensing
Warm-Up Time
1 minute (@ full specs 15 minute)
Coverage Area
7500 sq. ft. maximum
Pressure Dependence
+1.6% per 0.145 psi
Maintenance Interval
Maintenance free
Mounting Height
4-6' off the floor
Self-Diagnostics
Complete function check
Display (Optional)
Touch display, configurable color LCD with CO2 (PPM), Temperature (F or C), and Humidity (%RH)
Storage
-22 to 158 F (-30 to 70 C)
CO2 Accuracy
+/- 50 ppm (@ 1000 ppm, 63 to 82 F (17 to 28 C), 30 to 60% RH)
CO2 Sensing Method
Single beam non-dispersive Infrared (NDIR)
CO2 Sensor Life
More than 15 years (typical)
CO2 Response Time
3 minute diffusion time
CO2 Sensing Range
0 to 2000 ppm (CO2), optional 0 to 3000 ppm
Extended Range Accuracy
Typically (+/- 30 ppm +/- 20% of measured value)
CO2 Repeatability
+/- 20 ppm +/- 1% of measured value
CO2 Annual Zero Drift
+/- 0.3% of measurement range
CO2 Calibration
Senseair ABC algorithm (Automatic Baseline Correction)
Temperature Range
32 to 158 F (0 to 50 C)
Temperature Accuracy
+/-0.9 F @ 63 to 82 F, (+/- 0.5 C @ 17 to 28 C)
Temperature Repeatability
+/- 0.45 F @ 63 to 82 F, (+/- 0.25 C @ 17 to 28 C)
Temperature Response Time
6 minutes (Air velocity of 0.15m/s)
RH Sensor
Capacitive
RH Measurement Range
0-100%
RH Accuracy
+/- 5% @ 20 to 80% RH
RH Hysteresis
+/- 1% @ 20 to 80% RH
RH Annual Drift
+/- 0.5 % RH
RH Repeatability
+/- 0.25% RH @ 63 to 82 F, (+/- 0.25% RH @ 17 to 28 C)
RH Response Time